GATE 2020 · EE · MCQ · 1 mark · Power Systems › Switchgear & Protection

GATE 2020 Electrical Engineering question: A lossless transmission line with 0.2 pu reactance per phase uniformly distributed along…

A lossless transmission line with 0.2 pu reactance per phase uniformly distributed along the length of the line, connecting a generator bus to a load bus, is protected up to 80 % of its length by a distance relay placed at the generator bus. The generator terminal voltage is 1 pu. There is no generation at the load bus. The threshold pu current for operation of the distance relay for a solid three phase-to-ground fault on the transmission line is closest to:

  1. (A)

    1.00

  2. (B)

    3.61

  3. (C)

    5.00

  4. (D)

    6.25

Show answer

Official answer: D

Practise this question with exam-style marking