GATE 2020 · EE · NAT · 1 mark · Electrical Machines › Single-Phase Transformer

GATE 2020 Electrical Engineering question: A single-phase, 4 kVA, 200 V/100 V, 50 Hz transformer with laminated CRGO steel core has…

A single-phase, 4 kVA, 200 V/100 V, 50 Hz transformer with laminated CRGO steel core has rated no-load loss of 450 W. When the high-voltage winding is excited with 160 V, 40 Hz sinusoidal ac supply, the no-load losses are found to be 320 W. When the high-voltage winding of the same transformer is supplied from a 100 V, 25 Hz sinusoidal ac source, the no-load losses will be ______ W (rounded off to 2 decimal places).

Show answer

Official answer: 162.41 to 162.59