GATE 2020 set2 Mechanical Engineering question: Moist air at 105 kPa, 30°C and 80% relative humidity flows over a cooling coil in an…

Moist air at 105 kPa, 30°C and 80% relative humidity flows over a cooling coil in an insulated air-conditioning duct. Saturated air exits the duct at 100 kPa and 15°C. The saturation pressures of water at 30°C and 15°C are 4.24 kPa and 1.7 kPa respectively. Molecular weight of water is 18 g/mol and that of air is 28.94 g/mol. The mass of water condensing out from the duct is ________ g/kg of dry air (round off to the nearest integer).

Show answer

Official answer: 10

Practise this question with exam-style marking