GATE 2021 Instrumentation Engineering question: A bar primary current transformer of rating 1000/1 A, 5VA, UPF has 995 secondary turns.…
A bar primary current transformer of rating 1000/1 A, 5VA, UPF has 995 secondary turns. It exhibits zero ratio error and phase error of 30 minutes at 1000 A with rated burden. The watt loss component of the primary excitation current in ampere is __________ (rounded off to one decimal place).
Show answer
Official answer: 4.9 to 5.1