GATE 2022 · EE · NAT · 2 marks · Power Systems › Generation & Distribution

GATE 2022 Electrical Engineering question: Two generating units rated for 250 MW and 400 MW have governor speed regulations of 6%…

Two generating units rated for 250 MW and 400 MW have governor speed regulations of 6% and 6.4%, respectively, from no load to full load. Both the generating units are operating in parallel to share a load of 500 MW. Assuming free governor action, the load shared in MW, by the 250 MW generating unit is __________. (round off to nearest integer)

Show answer

Official answer: 188 to 192 or 198 to 202

Practise this question with exam-style marking