GATE 2023 Instrumentation Engineering question: A 1.999 V True RMS 3-1/2 digit multimeter has an accuracy of ±0.1 % of reading ±2…
A 1.999 V True RMS 3-1/2 digit multimeter has an accuracy of
±0.1 % of reading ±2 digits.
It is used to measure 100 A (RMS) current flowing through a line using a 100:5 ratio, Class-1 current transformer with a burden of 0.1 Ω ±0.5 %.
The worst-case absolute error in the multimeter output is __________ V (rounded off to three decimal places).
Show answer
Official answer: 0.009 to 0.011