GATE Assistant

Past questions › Engineering Sciences › GATE 2025

GATE 2025 · XE · NAT · 2 marks · Thermodynamics (XE4) › Mixtures of Ideal Gases & Psychrometry

GATE 2025 Engineering Sciences question: Air at 101 kPa, 15 °C and 50% relative humidity is first heated to 20 °C in a heating…

Air at 101 kPa, 15 °C and 50% relative humidity is first heated to 20 °C in a heating coil, and then humidified by spraying water on it. In the final state, the air has temperature of 25 °C and relative humidity of 85%. The amount of water sprayed (in gm per kg of dry air) is _______________ (rounded off to two decimal places).

Use the following data:

The saturation pressure of water at 15 °C = 1.7057 kPa

The saturation pressure of water at 25 °C = 3.1698 kPa

Show answer

Official answer: 11.5 to 12

Practise this question with exam-style marking