GATE 2026 · EE · MSQ · 1 mark · Electrical Machines › Single-Phase Transformer

GATE 2026 Electrical Engineering question: A 220V/12V single-phase transformer is designed for use in India and rated 100 VA at 50…

A 220V/12V single-phase transformer is designed for use in India and rated 100 VA at 50 Hz. Later, this unit is shipped to the USA where it is used as a 110V/6V transformer at 60 Hz.

Which of the following statements is/are correct?

  1. (A)

    No-load current drawn would be smaller for operation in the USA compared to that in India

  2. (B)

    For the same load current, the losses would be higher in the USA compared to that in India

  3. (C)

    The peak magnetic flux density in the core would be higher while operating in the USA compared to that in India

  4. (D)

    The eddy current losses in the core would be approximately 44% higher while operating in the USA compared to that in India

Show answer

Official answer: A